ADDITIONAL NOTES
1. The FR-320 releasing system will support the following items (ordered
separately):
a. Up to a 12V 12Amp Hr Battery
b. Class A converters ICAC-306, OCAC-302
c. Additional relays RM-312 (12) or RM-306 (6)
d. PR-300 module city tie & polarity reversal module
e. A combination of four (4) remote multiplexed LED annunciators & smart relays. The FR-320 does NOT support the RAM-300LCDW Series 300 LCD Annunciator
2. The Series 300 system is configured via the front panel switches without the need of a laptop computer. Use CFG-300. To retrieve the alarm (200) or event (200) logs the panel remotely the FR-320 must include a UDACT
3. The FR-320 will support all of the Mircom LED type annunciators
4. The FR-320 will charge up to a 26 Amp Hr Battery which requires a remote battery cabinet (BC-160)